QO/QOB Circuit Breakers Wire Sizes
Wire Sizes for QO/QOB Circuit Breakers
For additional information, refer to document number 0730CT9801 and QO and QOB Circuit Breakers online.
Wire Sizes for QO/QOB Circuit Breakers
|
Circuit Breaker Type |
Ampere Rating [1] |
Wire Size |
|---|---|---|
|
QO 1P |
10–30 A |
14–8 Al/Cu |
|
10–30 A |
(2) 14–10 Cu |
|
|
35–70 A |
8–2 Al/Cu |
|
|
QO 2P |
10–30 A |
14–8 Al/Cu |
|
10–30 A |
(2) 14–10 Cu |
|
|
35–70 A |
8–2 Al/Cu |
|
|
80–125 A |
4–2/0 Al/Cu |
|
|
150–200 A |
4–300 Al/Cu |
|
|
QO 3P |
10–30 A |
14–8 Al/Cu, (2) 14-10 Cu |
|
35–70 A |
8–2 Al/Cu |
|
|
80–125 A |
4–2/0 Al/Cu |
|
|
QOB-VH |
110–150 A |
4–300 Al/Cu |
|
QOT |
15–20 A |
12–8 Al 14–8 Cu |
|
QO-AFI, QO-GFI or QO-EPD |
15–30 A |
12–8 Al 14–8 Cu |
|
40, 50, 60 A |
12–4 Al 14–6 Cu |
|
|
QO-PL |
10–60 A |
12–2 Al 14–2 Cu |