EZ Meter-Pak Single-Phase Main Devices
Single-Phase, Three-Wire 120/240 Vac Meter Centers
Single-phase, Indoor/Rainproof, UL Listed
1200 A Main CB/Fusible Switch Devices come Standard with 2-STEP Removable Service Entrance Endwalls
Select EZM meter center short circuit current rating from EZM UL Listed Short-Circuit Current Ratings. Using this table as a reference, make the following selections:
-
Select EZM single-phase main device from Single-phase Main Devices or Single-phase Main Devices, EUSERC, with an equal or higher short circuit rating than the application.
-
Select EZM single-phase branch units from Single-Phase Branch Devices — NEMA 3R Construction.
-
Select proper 2P type QO, QO-VH, QOH, QBP-TM, QDP-TM, QGP-TM or QJP-TM branch circuit breakers for use as tenant mains in branch unit from and Tenant Circuit Breakers for EZM Branch Units .
-
Select accessories as required from Accessories for EZM Meter Centers.
-
Dimensions; see Dimensions for EZ Meter-Pak™ Meter Centers.
Select Main Devices—NEMA 3R Construction
Single-phase Main Devices
|
Ampere |
Service |
Horizontal Cross |
Cat. No. [1] |
Width |
Factory-Installed
Line Side Lug |
|
|---|---|---|---|---|---|---|
|
Main Circuit Breaker (single-phase Incoming and single-phase Outgoing) |
||||||
|
65 kA |
100 kA |
|||||
|
400 |
OH/UG |
400 A, Al |
— |
18.66 |
(1) 1–600 or (2) 1–250 |
|
|
600 |
OH/UG |
600 A, Al |
— |
18.66 |
(3) 3/0–500 |
|
|
800 |
OH/UG |
800 A, Al |
— |
18.66 |
(3) 3/0–500 |
|
|
1000 |
OH/UG |
1200 A, Cu |
— |
18.66 |
(3) 3/0–500 |
|
|
1200 |
OH |
1200 A, Al |
23.69 |
(4) 3/0-500 |
||
|
1200 |
UG |
1200 A, Al |
— |
23.69 |
(4) 3/0–500 |
|
|
1600 |
UG |
1200 A, Al/Cu |
22.48 |
6 (Order Lugs Separately) |
||
|
1600 |
OH/UG |
1200 A, Al/Cu |
30.19 |
(6) 1/0–750 or (12) 1/0–250 |
||
|
2000 |
OH/UG |
1200 A, Al/Cu |
— |
30.19 |
(6) 1/0–750 or (12) 1/0–250 |
|
|
2000 |
UG |
1200 A, Al/Cu |
— |
30.19 |
6 (Order Lugs Separately) |
|
|
Main Fusible Switches (Single-phase Incoming and Single-phase Outgoing) Requires 300 Vac Class T Fuses (Order Separately) |
||||||
|
400 |
OH/UG |
400 A, Al |
— |
18.66 |
(1) 1–600 or (2) 1–250 |
|
|
600 |
OH/UG |
600 A, Al |
— |
18.50 |
(3) 3/0–500 |
|
|
600 |
UG |
600 A, Al |
— |
20.46 |
2 (Order Lugs Separately) |
|
|
800 |
OH/UG |
800 A, Al |
— |
18.50 |
(3) 3/0–500 |
|
|
800 |
UG |
800 A, Al |
— |
20.46 |
2 (Order Lugs Separately) |
|
|
1200 |
OH |
1200 A, Al |
— |
23.69 |
(4) 3/0–500 |
|
|
1200 |
UG |
1200 A, Al |
— |
23.69 |
(4) 3/0–500 |
|
|
Main Lug Terminal Boxes (Single-phase Incoming and Single-phase Outgoing) |
||||||
|
225 |
OH/UG |
800 A, Al |
— |
11.66 |
(1) 4–300 |
|
|
400 |
OH/UG |
800 A, Al |
— |
17.15 |
(2) 3/0–500 |
|
|
600 |
OH/UG |
800 A, Al |
— |
17.15 |
(2) 1/0–750 or (4) 1/0–300 |
|
|
800 |
OH/UG |
800 A, Al |
— |
18.66 |
(4) 3/0–500 |
|
|
800 |
OH/UG |
800 A, Cu |
— |
24.08 |
(4) 3/0–500 |
|
|
1600 |
OH/UG |
1200 A, Al/Cu |
— |
22.48 |
(6) 1/0-600 or (12) 1/0-300 |
|
|
2000 |
OH/UG |
1200 A, Al/Cu |
— |
30.19 |
6 (Order Lugs Separately) |
|
|
Main Circuit Breaker (Single-phase Incoming and Single-phase Outgoing) with Energy Reduction Maintenance (ERMS) |
||||||
|
1200 |
UG |
1200 A, Al |
26.39 |
(4) 3/0–500 |
||
|
1200 |
OH |
1200 A, Cu |
— |
23.69 |
(4) 3/0–500 |
|
|
1600 |
OH/UG |
1200 A, Cu |
— |
30.19 |
(6) 1/0–750 or (12) 1/0–250 |
|
|
1600 |
UG |
1200 A, Al |
30.19 |
6 (Order Lugs Separately) |
||
|
2000 |
OH/UG |
1200 A, Cu |
— |
30.19 |
(6) 1/0-750 or (12) 1/0-250 |
|
|
2000 |
UG |
1200 A, Al |
— |
30.19 |
6 (Order Lugs Separately) |
|
Single-phase Main Devices, EUSERC
|
Ampere |
Service |
Horizontal Cross Bus Rating and Bus Bar Material |
Cat. No. |
Width |
Factory-Installed Lug Landings for use with Crimp-Type Lugs (2-Hole Mounting) Qty. per Phase and Neutral, except non-EUSERC. [8] |
|
|---|---|---|---|---|---|---|
|
Main Circuit Breakers (Single-phase Incoming and Single-phase Outgoing) [8] |
||||||
|
65 kA |
100 kA |
|||||
|
400 |
UG |
400 A, Al |
— |
20.46 |
1 (Order Lugs Separately) |
|
|
600 |
UG |
600 A, Al |
— |
26.19 |
2 (Order Lugs Separately) |
|
|
800 |
UG |
800 A, Al |
— |
26.19 |
2 (Order Lugs Separately) |
|
|
1000 |
UG |
1200 A, Cu |
— |
34.19 |
2 (Order Lugs Separately) |
|
|
1200 |
UG |
1200 A, Al |
32.39 |
3 (Order Lugs Separately) |
||
|
Main Fusible Switches (Single-phase Incoming and Single-phase Outgoing) [8] Requires 300 Vac Class T Fuses (Order Separately) |
||||||
|
400 |
UG |
400 A, Al |
— |
20.46 |
1 (Order Lugs Separately) |
|
|
600 |
UG |
600 A, Al |
— |
18.36 |
2 (Order Lugs Separately) |
|
|
1200 |
UG |
1200 A, Al |
— |
32.39 |
3 (Order Lugs Separately) |
|
|
Main Lug Terminal Boxes (Single-phase Incoming and Single-phase Outgoing) |
||||||
|
400 |
UG |
800 A, Al |
— |
17.16 |
1 (Order Lugs Separately) |
|
|
800 |
UG |
800 A, Al |
— |
25.16 |
2 (Order Lugs Separately) |
|
|
1200 |
UG |
1200 A, Al/Cu |
— |
33.16 |
3 (Order Lugs Separately) |
|
|
Main Circuit Breaker (Single-phase Incoming and Single-phase Outgoing) with Energy Reduction Maintenance Switch (ERMS) |
||||||
|
1200 |
UG |
1200 A, Al |
32.39 |
3 (Order Lugs Separately) |
||