Sepam™ Transformer Applications

Sepam Transformer Applications

T87

Advanced transformer protection is covered with the Sepam T87 and covers current, voltage, frequency, differential, and synchro check protection functions.

Advanced Protection Relay (T87 – Sepam 80 Series)

Typical Part Number: SQ1T87P1J5A0B0 Series 80 - Transformer Protection S84 (24-250 Vdc), mimicBus Graphical Display, 1/5A CT inputs, 14In/11Out Digital Module (110-125 Vdc/mid p.u.), 2 x RJ-45 ports (Modbus or IEC61850 with GOOSE), ladder logic firmware (PLC base).

Features

Feature

T87

Current Protection

●

Built in CB Control

●

Native Zone Selective Interlocking

●

Waveform Captures

●

Event Records

●

Voltage Protection

●

Frequency Protection

●

Field Expandable Communications

●

Synchro-check Protection (optional)

●

Native Automatic Throw over Scheme

●

Field expandable I/O

●

Ladder Logic PLC custom programming (optional)

●

Mimic-bus graphical display (optional)

●

Onboard data logging

●

Communications options

Modbus RTU

●

DPN

●

Modbus TCP/IP

●

IEC61850–MMS

●

IEC61850–MMS + GOOSE

●

Functions

ANSI Device Number

Description

T87

24

Volts/Hertz

●

25

Synch Check

●

26

Thermostat

●

27

Phase-to-phase undervoltage

●

27D

Positive sequence undervoltage

●

27R

Remnant Undervoltage

●

27S

Phase-to-neutral undervoltage

●

32P

Directional Power

●

38

Bearing Temperature

●

46

Negative Sequence Current/Unbalance

●

47

Negative Sequence undervoltage

●

49

Thermal Overload

●

49T

RTD Monitoring

●

50BF

Breaker Failure

●

50

Instantaneous Phase Overcurrent

●

50G

Instantaneous Ground Overcurrent (Measured)

●

50N

Instantaneous Ground Overcurrent (Calculated)

●

50V

Voltage Restrained Instantaneous  overcurrent

●

51

Time Phase Overcurrent

●

51G

Time Ground Overcurrent (Measured)

●

51N

Time Ground Overcurrent (Calculated)

●

59

Phase-to-phase overvoltage

●

59N

Neutral Voltage Displacement

●

63

Buchholz Pressure

●

64REF

Restricted Ground Fault

●

67N

Directional Ground Overcurrent

 

67

Directional Phase Overcurrent

●

81H

Overfrequency

●

81L

Underfrequency

●

87T

2 Winding Transformer Differential

●

Feedback